Description
- With lead sheath (LC)
- Armoured with galvanized steel tapes (GSTA) or aluminium tapes (ATA)
- Aliphatic and aromatic hydrocarbons resistant
Standards
International : IEC 60228; IEC 60332-3-22 Cat.A; IEC 60502-2Description
Applications
These power cables are used for electricity supply in medium voltage installation system. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protections are needed. The lead cover brings an enhanced resistance to aromatic hydrocarbons.
Design
Conductor:
Stranded bare copper (class 2)
Semi conductor
Insulation:
Cross-linked polyethylene (XLPE)
Semi conductor
Screen:
Copper tape
Bedding (optional):
An inner sheath acting as a filler with practically zero thickness
Inner sheath:
Polyvinyl chloride (PVC)
Lead cover (lead sheath)
Armour:
Paraffin-waxed crepe paper
Galvanized steel tapes (GSTA) or aluminium tapes (ATA) for 1 core cable
Outer sheath:
Polyvinyl chloride (PVC). Colour: red. Other colour on request
Core identification
1 core: natural
3x: black - green - brown (by tape under copper screen).
Marking
NEXANS 279 XLPE/PVC/LC/GSTA or ATA/PVC VOLTAGE Nber of cores and cross-section Cu/Alu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking.
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Bare copper |
| Type of conductor | Stranded, Class 2 |
| Insulation | XLPE (Cross-linked Polyethylene) |
| Screen | Copper tape |
| Inner sheath | PVC |
| Armour type | Galvanized steel tapes |
| Outer sheath | PVC |
| Lead Sheath | Yes |
| Protection | Yes |
| Dimensional characteristics | |
| Number of cores | 3 |
| Conductor cross-section | 95mm² |
| Conductor diameter | 11.35mm |
| Diameter over insulation | 21.55mm |
| Diameter over screen | 23.0mm |
| Diameter over inner sheath | 54.6mm |
| Diameter over lead sheath | 59.2mm |
| Diameter over armour | 63.0mm |
| Minimum outer diameter | 67.9mm |
| Maximum outer diameter | 74.9mm |
| Approximate weight | 12375kg/km |
| Electrical characteristics | |
| Rated Voltage Uo/U (Um) | 8.7 / 15 (17.5) kV |
| Mechanical characteristics | |
| Mechanical resistance to impacts | Good |
| Usage characteristics | |
| Fire retardant | IEC 60332-3-22 |
| Chemical resistance | Aliphatic and aromatic hydrocarbons resistant |
| Max. conductor temperature in service | 90°C |
| Operating temperature, range | -20 .. 60°C |
| U.V resistance | Yes |
Docs and info
Related documents
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
1 core: 10 x outer diameter
3 cores: 8 x outer diameter
To be double during laying operations
Aluminium conductors available on request.