Description
Standards
International : IEC 60227-2National : NF C 32-201/3
Description
Application
H07V-K cors are used for panels and cabinets stranding.
Installation
Open air, in conduit, in cable trunking, in cable ducting.
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Bare copper |
| Sheath colour | Red |
| Insulation | PVC |
| Conductor flexibility | Flexible class 5 |
| Dimensional characteristics | |
| Number of cores | 1 |
| Conductor cross-section | 2.5mm² |
| Maximum outer diameter | 4.2mm |
| Approximate weight | 33kg/km |
| Electrical characteristics | |
| Rated Voltage Uo/U (Um) | 450 / 750 V |
| Voltage drop, single phase | 14.7V/A.km |
| Permissible current rating in open air | 30A |
| Mechanical characteristics | |
| Mechanical resistance to impacts | Low |
| Cable flexibility | Flexible |
| Usage characteristics | |
| Max. conductor temperature in service | 70°C |
| Short-circuit max. conductor temperature | 160°C |
| Operating temperature, range | -5 .. 60°C |
| Weather resistance | Good |
| Flame retardant | C2, NF C 32-070 |
| Chemical resistance | Accidental |
| Water proof | Accidental |
| Bending factor when laying | 4(xD) |
| Length | 100m |
| Packaging | Coil |