Description
Standards
International : IEC 60502-2Description
Usage
IEC 60502-2 cables are for public power distribution network 12/20 kV.
Design
The cable is made of armoured or not armoured 1 core or 3 cores.
Insulation
The polyethylene cross-linking process ensures:
- Excellent heat resistance (90 °C)
- Good mechanical strength
- Excellent behaviour under short circuit conditions (250 °C)
- Extremely good resistance to low temperatures
Drumming
All drum types, lagged or not, up to a diameter of 3.40 m and a total weight of 12 t.
Characteristics
| Construction characteristics | |
|---|---|
| Conductor shape | Circular |
| Conductor flexibility | Stranded class 2 |
| Material of the external semi-conductor | Extruded strippable |
| Insulation | XLPE (chemical) |
| Material of the inner semi-conductor | Extruded |
| Screen | Copper tape |
| Material used for longitudinal water tightness | None |
| Outer sheath | PVC |
| Sheath colour | Black |
| Electrical characteristics | |
| Rated Voltage Uo/U (Um) | 12 / 20 (24) kV |
| Thermal resistivity of insulation | 3.5K*m/W |
| Insulation Relative dielectric coefficient | 2.5 |
| Dielectric loss factor (tand maxi =) | 40E-04 |
| Mechanical characteristics | |
| Mechanical resistance to impacts | Good |
| Cable flexibility | Rigid |
| Usage characteristics | |
| Short-circuit max. conductor temperature | 250°C |
| Max. conductor temperature in service | 90°C |
| Weather resistance | Good |
| Resistant to termites | No |
Docs and info
Selling information
Calculation assumptions (temperate countries):
- Air temperature : 30°C
- Soil temperature : 20°C
- Thermal resistivity of soil : 0.85 °K.m/W