Description
Standards
International : AEIC CS 6Description
Usage
C 33-226 cables are the new generation of cables for public power distribution network 12/20 kV.
Design
The cable is made of 3 bunched cores with a messenger.
Aluminium screen is made to ground short-circuit currents of EdF network, up to 1000 A for 1 s. for underground networks.
Marking
Example NEXANS - plant number- BGN5 NF C 33226 int. designation- section - Al - 12/20 (24) kV - year - month - installation guide type - G sheath thickness - SC semi-conductor thickness - EC screen thickness - C2 RT- installation temperature
Core identification: 1, 2, 3 helix-wise.
The marking is metric over one core sheath, as well as a tracing mark.
Characteristics
| Construction characteristics | |
|---|---|
| Sheath colour | Black + 2 Grey Lines |
| Conductor material | Aluminum |
| Material used for longitudinal water tightness | Swelling powder |
| Conductor flexibility | Stranded class 2 |
| Outer sheath | PE-HD |
| Insulation | XLPE (chemical) |
| Material of the external semi-conductor | Extruded strippable grooved elastomer |
| Protection | None |
| Material of the inner semi-conductor | Extruded |
| Screen | Longitudinal aluminium tape |
| Conductor shape | Circular |
| Dimensional characteristics | |
| Number of cores | 3 |
| Messenger cross-section | 50mm² |
| Electrical characteristics | |
| Rated Voltage Uo/U (Um) | 12 / 20 (24) kV |
| Mechanical characteristics | |
| Cable flexibility | Rigid |
| Usage characteristics | |
| Weather resistance | Good |
| Flame retardant | C2, NF C 32-070 |
| Resistant to termites | Yes |
Docs and info
Selling information
Options
C 33-226 cables can be manufactured with the following options:
- Copper conductor
- Other voltage
- Other section
- Grounding conductor
- Thicker aluminium screen
- Bunch + fibre optic element.